The DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DS250VG is one-pole SPD and can be used in common mode or common and differential mode.
DS250VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Electrical characteristics |
---|
SPD type follow test IEC 61643-11 |
1+2+3 | |
Network |
230/400 V 3-phase | |
AC system |
IT | |
Nominal line voltage |
230/400 Vac | |
Max. AC operating voltage L-N |
440 Vac | |
Temporary Over Voltage (TOV) Charasteristics – 5 sec. without disconnection |
580 Vac withstand | |
Temporary Over Voltage (TOV) Charasteristics – 120 mn without disconnection or with safety disconnection |
770 Vac withstand | |
Operating current LeakAge current at Uc |
none | |
Follow current |
none | |
Nominal discharge current 15 x 8/20 µs impulses |
30 kA | |
Max. discharge current max. withstand @ 8/20 µs by pole |
70 kA | |
Impulse current by pole max. withstand 10/350µs by pole |
25 kA | |
Total lightning current max. total withstand @ 10/350 µs |
75 kA | |
Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs – 8/20µs |
6 kV | |
Withstand on overvoltages IEEE C62.41.1 |
20 kV | |
Admissible short-circuit current |
50000A | |
Max. load current |
100 A | |
Connection mode |
L/PE | |
Protection mode(s) |
MC | |
Protection level @In (8/20µs) between L/PE |
– | |
Residual voltage @ In – 8/20µs waveform |
1.1 kV | |
Specific energy by pole max. withstand 10/350 µs |
156 kJ/ohm | |
Protection level L/PE |
1.5 kV | |
Protection level L/N for multipolar surge protector |
– |
Mechanical characteristics |
---|
Technology |
VG | |
SPD configuration |
3-phase | |
Connection to Network |
By screw terminals : 6-35 mm² / by bus | |
Format |
1-pole modular box assembled | |
Mounting |
Symmetrical rail 35 mm (EN60715) | |
Housing material |
Thermoplastic UL94-V0 | |
Operating temperature |
-40/+85°C | |
Protection rating |
IP20 | |
Outdoor application |
N | |
Failsafe behavior |
Disconnection | |
Disconnection indicator |
1 mechanical indicator by pole | |
Remote signaling of disconnection |
output on changeover contact |
Associated disconnection devices |
---|
Thermal disconnector |
internal | |
Installation ground fault breaker |
Type `S` or delayed | |
Fuses |
Fuses type gG – 315 A |
Standards compliance |
---|
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Certification | EAC |