The DS-HF is a secondary type 2 surge protector and RFI filter especially designed to protect sensitive equipment connected to single-phase networks.
The `surge protection` function is a completed by RFI filtering: this combination of functions result in enhanced efficiency against transient overvoltages and RF interferences.
It is connected in series on AC network, downstream of a primary type 2 SPD, installed in the main electrical switchboard, to protect a remote or sensitive equipment.
Citel model : DS-HF-120
Part Number : 77948
Electrical characteristics |
---|
SPD type follow test IEC 61643-11 |
2 (ou 3) | |
Network |
120 V single-phase | |
AC system |
TT-TN | |
Nominal line voltage |
120 Vac | |
Max. AC operating voltage L-N |
150 Vac | |
Temporary Over Voltage (TOV) Charasteristics – 5 sec. without disconnection |
180 Vac withstand | |
Temporary Over Voltage (TOV) Charasteristics – 120 mn without disconnection or with safety disconnection |
230 Vac disconnection | |
Operating current LeakAge current at Uc |
< 1 mA | |
Follow current |
none | |
Nominal discharge current 15 x 8/20 µs impulses |
3 kA | |
Max. discharge current max. withstand @ 8/20 µs by pole |
10 kA | |
Total Maximal discharge current max. total withstand @ 8/20 µs |
10 kA | |
Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs – 8/20µs |
10 kV | |
Withstand on overvoltages IEEE C62.41.1 |
10 kV | |
Admissible short-circuit current |
10000 A | |
RFI Filtering |
0.1 – 30 MHz | |
Max. load current |
16 A | |
Connection mode |
L/N/PE | |
Protection mode(s) |
MC/MD | |
Protection level CM/DM @In (8/20µs) and @ 6kV (1.2/50µs) |
0.6 kV/0.5 kV |
Mechanical characteristics |
---|
SPD configuration |
Single phase | |
Connection to Network |
by screw terminals: 0.75 – 4 mm² | |
Format |
Plug-in modular box | |
Mounting |
Symmetrical rail 35 mm (EN60715) | |
Housing material |
Thermoplastic UL94-V0 | |
Operating temperature |
-40/+85°C | |
Protection rating |
IP20 | |
Outdoor application |
N | |
Failsafe behavior |
Disconnection SPD – Signaling | |
Disconnection indicator |
Green led(s) off | |
Voltage/operating indicator |
Green led(s) on | |
Remote signaling of disconnection |
none |
Associated disconnection devices |
---|
Thermal disconnector |
internal | |
Installation ground fault breaker |
Type `S` or delayed | |
Fuses |
Fuses type gG – 20 A max. (if necessary) |
Standards compliance |
---|
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Certification | EAC |