DS70R type 2 AC surge protector are used mainly for primary protection of single and three-phase networks at the main electrical panel.
They provide common-mode protection and are available in one-phase, single-phase, 3-phase and 3-phase+Neutral.
This SPD is based on association of high energy varistors equipped with thermal disconnector and failure indicator, to comply with standards.
The DS70R surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks. Each pole of the SPD is connected between Line(s) and PE and Neutral and PE.
Citel model : DS73R-600
Part Number : 321503
Electrical characteristics |
---|
SPD type follow test IEC 61643-11 |
2 | |
Network |
480/690 V Triphasé+PE (Delta) | |
AC system |
TNC | |
Nominal line voltage |
480 Vac | |
Max. AC operating voltage L-N |
840 Vac | |
Temporary Over Voltage (TOV) Charasteristics – 5 sec. without disconnection |
700 Vac w | |
Temporary Over Voltage (TOV) Charasteristics – 120 mn without disconnection or with safety disconnection |
920 Vac disconnection | |
Operating current LeakAge current at Uc |
< 1 mA | |
Follow current |
none | |
Nominal discharge current 15 x 8/20 µs impulses |
30 kA | |
Max. discharge current max. withstand @ 8/20 µs by pole |
70 kA | |
Total Maximal discharge current max. total withstand @ 8/20 µs |
210 kA | |
Admissible short-circuit current |
25000 A | |
Connection mode |
L/PE | |
Protection mode(s) |
MC | |
Protection level @In (8/20µs) between L/PE |
1.8 kV | |
Protection level L/PE |
1.8 kV |
Mechanical characteristics |
---|
Technology |
MOV | |
SPD configuration |
3-phase+PE | |
Connection to Network |
By screw terminals: 2.5-25 mm² / by bus | |
Format |
Plug-in modular box | |
Mounting |
Symmetrical rail 35 mm (EN60715) | |
Housing material |
Thermoplastic UL94-V0 | |
Operating temperature |
-40/+85°C | |
Protection rating |
IP20 | |
Outdoor application |
N | |
Failsafe behavior |
Disconnection | |
Disconnection indicator |
2 mechanical indicators by pole | |
Spare module |
DSM70R-600 | |
Remote signaling of disconnection |
none |
Associated disconnection devices |
---|
Thermal disconnector |
internal | |
Installation ground fault breaker |
Type `S` or delayed | |
Fuses |
Fuses Type gG – 100 A |
Standards compliance |
---|
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Certification | EAC |